Horsepower: 1 to 250 HP
(0.75 to 185kW)
Supply Power:
Three Phase: 208, 240, 400, 480 or 590VAC
50 or 60 Hz (+10/-15%) or, can operate from
a single-phase source with (1.73 derate).
Motors: The MCH adjustable speed drives are designed to operate standard polyphase
induction motors rated for
200, 230, 400, 460 or 575VAC from 0 to
120Hz.
Enclosure: NEMA 1 is standard for drive & options
NEMA 12 available for drive only.
Standard Features
Easy set-up and operation: The MCH adjustable frequency drives offers intuitive
operator interface using plain English programming and operational information.
2-line, 32 character backlit display
Keypad with H-O-A operation
Personal computer interface using
AC Techs free TechLink Software
PID set point control: Let the drive software adjust the motor speed to maintain a
preset pressure, flow, temperature or other independent variable.
Remote enable/disable
Direct or reverse acting
Transducer calibration
High/Low level alarm
Motor Thermal Overload: The MCH includes UL and cUL
approved motor protection device for single motor applications.
MCH
Installed Options
Pre-Engineered and factory installed, MCH options are
"Contractor Ready" providing the following benefits:
- Rugged steel enclosure with hinged cover.
- Plenty of knockouts that allow for top or bottom conduit runs.
- Generous wire ways.
- Oversized terminal strip duplicates all the VFD terminals with plug connections that
allow easy removal of the MCH Series without disturbing any field wiring.
Branch Circuit Protection:
Choose either a Circuit Breaker or Disconnect with fusing, both offer door interlocked
rotary handle. If branch circuit protection is located elsewhere, door interlocked
disconnect switch is available without fusing.
Input Line Reactor:
The most recommended complement to a good adjustable frequency drive installation. The
input reactor adds protection for the drive against common electrical noise and line
spikes while reducing noise and harmonics back to the supply mains.
Drive Bypass:
Three-contactor drive bypass completely isolates the adjustable speed drive when
operating the motor at full speed directly across the line. Contactor logic and controls
are operated at 115VAC and include pilot light operators and door mounted controls.